Dispersion of Microbes from Floors when Walking in Ventilated Rooms

The redispersion factor of microbe-carrying particles, which is the ratio of the concentration of floor-derived microbes in room air to those on a floor surface, was determined, as was the percentage of floor-derived microbes in room air. These relationships were shown to vary according to conditions in the room. Equations were derived that allow these relationships to be calculated for a variety of room conditions, including air supply rates, levels of personnel activity, and the effect of gravitational deposition on microbe-carrying particles.