Submitted by Maria.Kapsalaki on Mon, 06/23/2014 - 14:39
To improve the energy performance of a district heating and cooling (DHC) plant, the expected performance of the plant was studied using simulations based on mathematical models. A model of the entire heat source system with an embedded module that automatically determines the on/off status of heat source equipment using cooling/heating loads was developed and validated using measured actual performance data. The mean error between the simulated and measured total energy consumption was 4.2%.