Reports investigation of the relative effectiveness of wall gratings and flues as means of naturally ventilating unheated closed rooms. Ventilation rates of several rooms were measured using carbon dioxide as tracer gas and wind speed and direction were recorded. Presents results and finds for the flue, ventilation increased with wind speed irrespective of direction. For grating, ventilation rate increases slowly with size of grating and is dependent on both wind speed and direction. Concludes flue with base opening of 15 sq.ins. is as efficacious as grating having 50 sq.ins. in free area.
The natural ventilation of unheated closed rooms.
Year:
1945
Bibliographic info:
Jnl. of Hygiene vol.44 p.314-325.