Turiel I. Rudy J.
Year:
1980
Bibliographic info:
Report No. LBL-10496 April 1980 20pp. 11 refs. 4 figs. 1 tab. #DATE 01:04:1980 in English

Uses occupant-generated CO2 as an indicator of the actual ventilation rate in a San Francisco office building. Employs two techniques, a decay method and an integral method, and measurements are conducted simultaneously at several locations. The decay method compares favourably with the conventional measurement methods in both the all-outside-air and recirculation modes, whereas the integral method shows a considerable deviation from the other methods in the recirculation mode. Both techniques show promise of being suitable methods for measuring ventilation rates in commercial and institutional buildings.