Brohus H, Nielsen P V
Year:
1996
Bibliographic info:
Indoor Air, No 6, 1996, pp 157-167

Personal exposure in a displacement ventilated room is examined. The stratified flow and the considerable concentration gradients necessitate an improvement of the widely used fully mixing compartmental approach. The exposure of a seated and a standing person in proportion to the stratification height is examined by means of fullscale measurements. A breathing thermal manikin is used to simulate a person. It is found that the flow in the boundary layer around a person is able to a great extent to entrain and transport air from below the breathing zone. In the case of non-passive, heated contaminant sources, this entrainment improves the indoor air quality. Measurements of exposure due to a passive contaminant source show a significant dependence on the flow field as well as on the contaminant source location. Poor system performance is found in the case of a passive contaminant released in the lower part of the room close to the occupant. A personal exposure model for displacement ventilated rooms is proposed. The model takes the influence of gradients and the human thermal boundary layer into account. Two new quantities describing the interaction between a person and the ventilation are defined.