This study was conducted to determine how sash movements affect the performance of fume hoods. The performance of two fume hoods was studied as the sashes were moved from closed to open position at speeds of 2 ft/s, 1.5 ft/s, and 1 ft/s. The tests were conducted with fume hoods operated at both constant volume and variable air volume. The tests indicate that sash movements can disturb airflow patterns at the face of the hood and potentially affect the performance of the hood. The effect of the sash movement varied with hood type and speed of sash movement. The faster sash movements of 2 ft/s and 1.5 ft/s had a greater effect on the performance of the hoods than the slower movement of 1 ft/s. Constant-volume hoods and variable-air volume hoods were both affected by sash movements. Constant volume hoods set to a full open face velocity of 60 ft/min were more susceptible to the sash movement than at 100 ft/min full open face velocity. The performance of variable-air-volume hoods is affected not only by sash movement speed but also by the response time of the controller. The drop in face velocity that occurs when the sash is moved is determined by the speed of the VA V controller. The required response time for containment depends on the fume hood design and the speed of the sash movement.
A study on how sash movement affects performance of fume hoods.
Year:
1997
Bibliographic info:
USA, Ashrae Transactions, Vol 103, Part 2, 1997, proceedings of the Ashrae Summer Meeting, Boston, 29 June - 2 July, 1997 [preprint].