Glicksman L R, Taub S
Year:
1997
Bibliographic info:
UK, Energy and Buildings, No 25, 1997, pp 243-249

Occupant-controlled heating, ventilating and air conditioning (HVAC) systems allow inhabitants of open-plan spaces some degree of control over their immediate microclimate. Typically, cooled air is supplied at floor or desktop levels. The amount and direction of air flow is under occupant control. Productivity increases have been attributed to this form of control. This paper proposes a simplified model of the thermal environment created by an occupant-controlled HV AC system and the behavior of the occupants within it. The thermal environment is characterized by individual nodes representing sub-areas of the conditioned space and a single well-mixed ceiling space above the occupied zone. Random processes are used to simulate the comings and goings of individual occupants and their HV AC control behavior. The model is used to identify the parameters which have the largest influence on the energy efficiency. Energy use of task HY AC with occupant sensors is found to be less than that of a conventional HVAC system by 13%. Individual HVAC control requires about 10% more energy than uniform temperature conditions.