Martin A J, Booth W B
Year:
1996
Bibliographic info:
UK, Building Services Research and Information Association (BSRIA), Technical Note TN 1/96, 1996

Demand controlled ventilation systems can be used to minimise energy consumption whilst maintaining satisfactory levels of indoor air quality (IAQ). As an alternative to C02 sensors IAQ sensors (based on Taguchi mixed gas sensors) can be used to infer levels of IAQ. This Technical Note provides details of a series of laboratory and site tests to determine the performance of a range of IAQ sensors. As part of laboratory tests the IAQ sensors demonstrated relatively high correlation coefficients when tested against single pollutants; however, coefficients corresponding to test data over periods when the sensors were subjected to non-controlled conditions (ie a wide range of non-controlled pollutants) demonstrated a poor relationship when there was no single predominant pollutant. Site monitoring in three buildings demonstrated relatively poor correlation coefficients between the IAQ sensors and monitored gases due to the unquantifiable presence of other pollutants. The strongest correlations between IAQ sensors and pollutant gases were obtained when a pollutant gas was present in a sufficient concentration to pervade the complete atmosphere of a zone. The site monitoring demonstrated that the dilution of pollutants in the indoor environment may be carried out at the expense of introducing polluted air from the outside. A major source of pollution to affect the monitored sites was from vehicle traffic (indicated by levels of CO). The use of C02 controlled ventilation techniques is more effective than those using IAQ sensors in applications where IAQ is primarily influenced by varying occupancy.