Liu M, Zhu Y, Park B Y, et al
Year:
1999
Bibliographic info:
USA, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (ASHRAE), 1999, in: the ASHRAE Transactions CD, proceedings of the 1999 ASHRAE Winter Meeting, held Chicago, USA, January 1999

To remedy comfort problems in a 99,000 fi2 (9,200 m2) office building, the total airflow rate was reduced by 35%, and the total outside airflow was reduced by 86% in four multi-zone air-handling units that serve the office building. After the airflow reduction, the peak room relative humidity level was reduced from 70% to 55%, and cold and hot deck reset schedules were implemented. These improved operating practices reduced building energy consumption by 27%.