Noh K.C, Jang J.S., Oh M.D
Year:
2007
Bibliographic info:
Building and environment, Vol 42, Issue 2, February 2007, pp 689-698

For that paper, experimental and numerical studies on thermal comfort and indoor air quality were performed in a lecture room with cooling loads when the operating conditions are changed. The results have been compared and showed a reasonable agreement with each other. From those results, the authors found that the increment of the discharge angle of 4-way cassette-air conditioner makes uniformity of the thermal comfort worse, but scarcely affects IAQ. The variation of the discharge airflow rarely affected thermal comfort and IAQ