Submitted by Maria.Kapsalaki on Fri, 10/25/2013 - 19:15
Aerosol detection in HVAC duct components is a critical component of contaminant detection and analysis. Incorrect placement of a sensor inlet within the ductwork can have a significant, deleterious effect on capture efficiency and sample accuracy. Computational fluid dynamics studies were conducted of straight rectangular cross-section ductwork and a 90° bend to determine flow patterns and simulations of particulate injections were made at various locations across the inlet. The resultant particle distributions were analyzed to determine the optimal placement for a sensor inlet.