Submitted by Maria.Kapsalaki on Mon, 02/10/2014 - 08:57
The redispersion factor of microbe-carrying particles, which is the ratio of the concentration of floor-derived microbes in room air to those on a floor surface, was determined, as was the percentage of floor-derived microbes in room air. These relationships were shown to vary according to conditions in the room. Equations were derived that allow these relationships to be calculated for a variety of room conditions, including air supply rates, levels of personnel activity, and the effect of gravitational deposition on microbe-carrying particles.
Submitted by Maria.Kapsalaki on Mon, 10/28/2013 - 10:28
The removal efficiency of high efficiency air filters against microbe-carrying particles (MCPs) in the air supply of occupied rooms, such as cleanrooms, was determined. Knowing the size distribution of MCPs in the air to be filtered, and the removal efficiency of a filter against individual particle diameters, the overall removal efficiency was ascertained.