Discusses the two methods for calculating air infiltration given in the ASHRAE handbook. These are the air change method, a gross estimate based on the number of windows and doors in each room, and the crack method based on measurements of flow through the cracks around windows and doors. Presents comparisons of tracer gas measurements with calculations by both air change and crack methods for test houses in California and Minnesota. Find agreement is adequate for sizing equipment but that the crack method underestimates infiltration at low wind velocity.
Calculating infiltration : an examination of handbook models.
Year:
1980
Bibliographic info:
ASHRAE Trans. 1980 vol.86 part 2 1980 p.751-764