This paper characterizes the relationship between occupant activities and indoor air particulate levels in a non-smoking office building. Occupant activities were recorded on video. Particulate concentrations were monitored by three optical particle counters (OPCs) in five size ranges at three heights. Particulate mass concentrations were measured gravimetrically and bioaerosol concentrations were determined by impaction methods. Occupant activities and number concentrations were determined with 1-min resolution over a 1-week period. Occupant activities such as walking past or visiting the monitoring site explained 24-55% of the variation of 1- to 25-μm diameter particle number concentrations. Statistical models associating particulate concentrations with occupant activities depended on the size fraction and included an autocorrelative term. Occupant activities are estimated to contribute up to 10 μg m-3 in particulate concentrations per person. Number concentrations of particles smaller than 1 μm had little correlation with indoor activities other than cigarette smoking and were highly correlated with outdoor levels. The method can be used to characterize emissions from activities if rapid measurements can be made and if activities can be coded from the video record.
Characterization of particulate emissions from occupant activities in offices.
Year:
2001
Bibliographic info:
Indoor Air, No 11, 2001, pp 35-48