Discusses acceptable levels of CO2 contamination in occupied rooms. Describes measurements in a classroom over 3 days using an infra-red analyser with natural ventilation via the windows. Illustrates curves for CO2 concentrations in 8 graphs for closed windows. Notes that limiting value of 0.1% by volume CO2 (1000ppm) is reached in from 5 to 15 minutes. Repeated sudden ventilation by opening windows is not practicable. Evaluates air change rate. Concludes energy saving for ventilation in heavily populated rooms is only attainable by mechanical ventilation with heat recovery. Ventilation periods greater than 7 minutes increase energy consumption for no gain in air quality.
Investigating CO2 concentrations in a classroom. Untersuchung der CO2 Konzentration in einem Klassenraum.
Year:
1980
Bibliographic info:
Gesundh-Ing. August 1980 vol.101 no.8 p.225-228