Yuan X, Chen Q, Glicksman L R, et al
Year:
1999
Bibliographic info:
USA, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (ASHRAE), 1999, in: the ASHRAE Transactions CD, proceedings of the 1999 ASHRAE Winter Meeting, held Chicago, USA, January 1999

This paper presents a set of detailed experimental data of room airflow with displacement ventilation. These data were obtained from a new environmental test facility. The measurements were conducted for three typical room configurations: a small office, a large office with partitions, and a classroom. The distributions of air velocity, air velocity fluctuation, and air temperature were measured by omnidirectional hotsphere anemometers, and contaminant concentrations were measured by tracer gas at 54 points in the rooms. Smoke was used to observe airflow. The data also include the wall surface temperature distribution, air supply parameters, and the age of air at several locations in the rooms. A computational fluid dynamics (CFD) program with the Re-Normalization Group (RNG) k-e model was also used to predict the indoor airflow. The agreement between the computed results and measured data of air temperature and velocity is good. However, some discrepancies exist in the computed and measured concentrations and velocity fluctuation.