Cermak R, Majer M, Melikov A
Year:
2002
Bibliographic info:
Proceedings of Indoor Air 2002 (9th International Conference on Indoor Air Quality and Climate) - June 30 - July 5, 2002 - Monterey, California - vol 4, pp 1054-1059, 1 fig, 10 refs, 1 tab

This paper examines the performance of five different air terminal devices for personalized ventilation in relation to the quality of air inhaled by a breathing thermal manikin in a climate chamber. The personalized air was supplied either isothermally or non-isothermally (6 C cooler than the room air) at flow rates ranging from less that 5 l/s up to 23 /s. The air quality assessment was based on temperature measurements of the inhaled air and on the portion of the personalized air inhaled. The percentage of dissatisfied with the air quality was predicted. The results suggest that regardless of the temperature combinations, personalized ventilation may decrease significantly the number of occupants dissatisfied with the air quality. Under non-isothermal conditions the percentage of dissatisfied may decrease up to 4 times.