Flow and heat transfer calculations have been operated in a typical office room equipped with a displacement ventilation and a chilled ceiling system. Results show quasi-periodic flow when the values of internal thermal loads are high. They also show lateral oscillations of the plumes above heat sources which create after impact on the cold ceiling recirculating flows in the room.
Numerical investigation of transient buoyant flow in a room with displacement ventilation and a chilled ceiling system
Year:
2001
Bibliographic info:
International Journal of Heat and Mass Transfer, Vol 44, 2001, n. 16, pp 3067-3080, fig, tab, 19 refs