Naydenov K, Pitchurov G, Langkilde G, Melikov A
Year:
2002
Bibliographic info:
Proceedings of Room Vent 2002 (8th International Conference on Air Distribution in Rooms) - 8-11 september 2002 - Moltke's palace, Copenhagen - Denmark - pp 483-486, 3 Fig., 9 ref.

This paper gives the results of a field study in Danish office spaces with displacement ventilation systems. Draught was identified as a serious problem. Half of the 227 occupants were not satisfied with indoor air quality. Occupants counteract draught discomfort in blocking air supply diffusers or asking the maintenance staff to increase the supply air temperature. So a very careful design for displacement ventilation is required in order to perform satisfactorily in practice. Employees should be informed about the ventilation principle and become active in achieving a high quality indoor environment.