Wind pressures on three Navy buildings at the Kanehoe Marine Corp Air Station, Hawaii were measured. Indoor and outdoor variables were also measured including temperature, dry bulb, wet bulb, relative humidity, wind speed, and wind direction. Pressure measurements were carried out using Validyne DP103 pressure transducers, and a static pressure probe. Natural ventilation is estimated 1. by combining window areas and pressure coefficients with wind speed and 2. using the LBL infiltration model.
Project Report. Field testing of wind cooling effects on Navy buildings
Year:
1983
Bibliographic info:
USA, University of California. Lawrence Berkeley Laboratory. Report No. LBL 14925, 1983, 37pp, 20 figs, 7 tabs, 10 refs. #DATE 01:05:1983, in English,