Natural ventilation in the modern hospital.

Assesses the role of natural ventilation in modern hospitals. Considers optimum standards of air change rates for winter and summer conditions and reviews factors within the hospital context that are likely to affect the achievement of natural ventilation. Notes an air change rate of 1.5/hr. is usually assumed for heat loss calculation. Finds cross ventilation is unlikely to be achieved and designs should be based on single sided ventilation. Reports tracer gas measurements of natural ventilation in Southland Hospital, Shoreham by Sea.

Natural ventilation of large hospital buildings.

Wind-tunnel tests of hospital scale models and a computer program to calculate internal air flows were used to produce aprediction technique to determine the rates of natural ventilation of large hospitals. Technique was applied to aharness hospital design and article reports that the ventilation generated by wind forces in for instance, ward areas would not be consistently adequate for the comfort and well-being of the occupants.

Comparison of internal and outside pressure distributions measured at a model and at the actual slotervaart hospital in amsterdam.

Reports measurements of air pressure differences to determine influence of wind on air flow directions through door and window gaps. Studies measures to prevent air transport between the 4 wings of the cross-shaped hospital and to ensure air flows from the corridors to the rooms on both sides. Pressure differences measured between facades agreed well with wind-tunnel results. Air flow directions measured agreed with results from an electrical analogue ventilation model.