Jones R. Fagan R.
Year:
1974
Bibliographic info:
ASHRAE Journal, vol.16 no.8 p.49-53

Uses Turk's equation to obtain CO concentration v time curves in an office and a one-family house. Compares results with similar studies, current threshold limit values and ambient air quality standards for CO. Finds model is apparently valid for CO and probably for other gaseous contaminants not affected by absorption or deposition. Concludes that commercial environments should have at least 5 cfm fresh air per occupant and that a value of 50 cfmfresh air appears to be adequate for a one-family dwelling. Gives table showing suggested ventilation rates for different buildings with different levels of smoking.