Shaw C.Y.
Year:
1983
Bibliographic info:
NRCC Building Research Note no.204 July 1983 #DATE 01:08:1983 in English

Measures air change rates in a 2-storey detached house with operation of various types of mechanical fresh air ventilation systems. Studies 4 systems, including 2 balanced systems and 2 exhaust-only systems. The forced ventilation rate is controlled at 0.15, 0.25, 0.4, or 0.5 ach. Develops expressions for the test house relating the house air change rate under winter conditions to the forced ventilation rate and the infiltration rate due to wind and temperature difference.