Klaas De Jonge, Jelle Laverge
Year:
2019
Languages: English | Pages: 11 pp
Bibliographic info:
40th AIVC - 8th TightVent - 6th venticool Conference - Ghent, Belgium - 15-16 October 2019

With increasing building airtightness, the design of an adequate ventilation system gains importance. The first generation of ventilation systems, based on continuous supply of the nominal airflow rate, are now being replaced by Demand Controlled Ventilation (DCV). These systems, often H2O and/or CO2 controlled, do not take into account the emissions of Volatile Organic Compounds (VOCs) to the indoor environment.

A small, airtight, zero energy building that has been designed as the Belgian contribution to the international Solar Decathlon competition (2011) was rebuilt afterwards in Ostend, Belgium. This building will be used as test facility for the development and validation of a holistic VOC source model. In this study, results are obtained from thermal, airflow and contaminant simulation models of the test facility. The different models and modeling assumptions are discussed. A dynamic VOC source model, derived from literature, is used as proxy of possible VOC concentrations.

The results show an important influence of environmental parameters on the indoor VOC levels with VOC concentrations exceeding health guidelines. It is therefore important to design DCV systems and controls taking into account possible elevated VOC levels and while doing so, incorporate the dynamic behavior (influence of temperature and humidity) of the VOC emissions.