The main task of every ventilation system is to dilute and extract pollutants from indoor air, most importantly in occupied space. This is usually achieved by exchanging polluted indoor air with less polluted outdoor air. In the case of a mechanical ventilation system, this process requires a fan power to be provided which is approximately proportional to the power of three to the resulting airflow. Because of this, reducing the necessary airflow to be provided by the ventilation unit e.g., by 10% would lead to a reduced power supply of about 27%. Vice versa, a necessary increase of 10% of the airflow provided by the unit, would result in an increased power supply of about 33%. To determine whether a reduced unit airflow is feasible or an increase in unit airflow is required, it is important to evaluate the ventilation efficiency for the occupied zone and any other zone with certain air change rate requirements. Unfortunately, this evaluation process is time-consuming as well as labour-intensive and can't
be done for every indoor zone separately yet. However, for those situations where it has been performed, a common procedure for comparing them in a comprehensible graphical way would be helpful. This paper proposes a diagram to visualize how efficiently certain ventilation systems provide their unit air change rate as a room air change rate.
As characteristic physical limits and isolines the values for ideal mixed ventilation and plug flow are included as
well. Furthermore, the diagram has been applied to visualize air change rates from a literature review. The overview indicates, other than often assumed, real buildings do not necessarily reach ideally mixed ventilation.
Pointing out that, it must be admitted as well, that currently the available data for such a comparison is often not based on a uniform measurement and evaluation procedure. Nevertheless, the proposed diagram can be a useful tool to communicate the air exchange performance of ventilation systems.
Proposal of an effort-benefit diagram to compare unit and room air-change rates applied to a literature review
Year:
2023
Languages: English | Pages: 9 pp
Bibliographic info:
43rd AIVC - 11th TightVent - 9th venticool Conference - Copenhagen, Denmark - 4-5 October 2023