Fleury E, Millet J R, Villenave J G, Veyrat O, Morisseau C
Year:
1998
Bibliographic info:
Sweden, Stockholm, KTH Building Services Engineering, 1998, proceedings of Roomvent 98: 6th International Conference on Air Distribution in Rooms, held June 14-17 1998 in Stockholm, Sweden, edited by Elisabeth Mundt and Tor-Goran Malmstrom, Volume 1

The air leakages can have a large impact on heating needs and thermal comfort in industrial buildings. This is sometimes poorly taken into account, both due to the lack of theoretical approach and knowledge of air tightness. We present the application of the calculation code SIREN95 in this field and its validation against field measurements.""The field study concerns five average industrial buildings, in which different tasks have been carried out: air tightness measurements, using pressurisation method, two series of measurements of air change with a tracer gas method (decay), field measurements during a whole heating season.""Weekly energy balances were calculated using the results of field measurements - and the air changes calculated by SIREN95. They showed a good agreement between heat gains (internal and solar) and heat losses (through the envelope, air change).