Meyringer V
Year:
1985
Bibliographic info:
Condensation and Energy Problems: A Search for an International Strategy. Workshop, Leuven, 23-25 September 1985.

Discusses ventilation efficiency and production rates of water vapour in residential buildings, using a three person flat of 100 m2 living area as amodel. The cold outer surfaces of a building are the critical ones regarding condensation. To avoid surface condensation, the ventilation requirement is that the air change rate must reduce the vapour content in the room air at least so far as to reduce the dew point temperature below the lowest surface temperature. The minimum air change rate required has been calculated for some typical meteorological situations, assuming complete mixing of the room air.